<abbr id="00ggy"><source id="00ggy"></source></abbr>
  • 
    
    <strike id="00ggy"></strike>
  • <bdo id="00ggy"></bdo>
  • <li id="00ggy"><source id="00ggy"></source></li>
  • <li id="00ggy"><source id="00ggy"></source></li>
    Search for the product you are looking for
    研發中心

    News

    Slide down

    Failure Mechanisms of Cooling Loss in Thermal Shock Test Chambers ——A Systematic Analysis Based on the Reverse Carnot Cycle

    Source:LINPIN Time:2025-09-04 Category:Industry News

     

    Thermal shock test chambers are indispensable in reliability qualification for electronics, aerospace, and automotive industries. Once the “no-cooling” fault occurs, the test sequence is immediately interrupted and secondary damage to the specimen may follow. Using the reverse Carnot cycle as the theoretical backbone and integrating years of field-maintenance data, this paper systematically reviews the macroscopic manifestations, microscopic mechanisms and discriminating methods of cooling loss, and puts forward actionable preventive-maintenance strategies. The findings provide laboratory operators with rapid fault-location and handling guidelines, and also offer equipment manufacturers a reference for reliability-oriented design.

    Thermal Shock Test Chambers
    1?Introduction
    By rapidly shuttling specimens between high- and low-temperature zones, thermal shock chambers expose latent defects through extreme thermal gradients [1]. Continuous low-temperature holding relies on the correct operation of the reverse-Carnot refrigeration cycle. When this cycle is disturbed, cooling capacity is lost. Although manufacturers perform multiple verifications before shipment, long-term operation under grid disturbances, mechanical wear and refrigerant ageing can still trigger sudden cooling failures. Clarifying the failure mechanisms and establishing a standardized troubleshooting workflow are therefore essential for ensuring test accuracy and minimizing downtime.
    2?The Reverse Carnot Cycle and System Architecture
    2.1?Cycle Theory
    The reverse Carnot cycle comprises two isothermal and two adiabatic processes [2]. In a test chamber the cycle is decomposed into four stages:
    (1) Adiabatic compression: low-pressure refrigerant vapour is compressed to high pressure and temperature;
    (2) Isobaric heat rejection: superheated gas condenses in the condenser, transferring heat to the coolant medium (air or water);
    (3) Adiabatic expansion: liquid refrigerant passes through a throttling device (capillary or electronic expansion valve) and experiences a sharp pressure and temperature drop;
    (4) Isobaric heat absorption: low-pressure two-phase refrigerant evaporates in the evaporator, removing heat from the specimen and chamber walls before returning to the compressor.
    2.2?System Configuration
    A typical three-zone chamber consists of a hot zone, a cold zone and a specimen transfer basket. The refrigeration system is usually a two-stage cascade:
    (1) High-temperature stage: R404A or R507 for precooling and medium-temperature holding;
    (2) Low-temperature stage: R23 or R508B for deep cooling below ?55 °C;
    (3) Switching devices: hot-gas-bypass solenoid valve, intermediate heat exchanger and check valves for inter-stage coupling and load matching.
    3?Macroscopic Symptoms of Cooling Failure
    3.1?Temperature Anomaly
    When the set point is ?40 °C but the chamber remains above ?20 °C after 30 min and the cooling rate is <1 °C·min?1, insufficient capacity is diagnosed.
    3.2?Pressure Anomaly
    High-side pressure <1.0 MPa or negative low-side pressure indicates cycle imbalance. 3.3?Compressor Behaviour Motor current drops >20 % below rated value or the protector trips repeatedly.
    4?Systematic Analysis of Failure Mechanisms
    4.1?Compressor Faults
    4.1.1?Electrical Factors
    Voltage sags or harmonic distortion can erode contactor contacts and prevent coil pull-in; phase loss raises winding temperature and triggers the internal thermal protector.
    4.1.2?Mechanical Factors
    Wear of scroll tip seals, broken piston rings or increased crankshaft eccentricity reduce volumetric efficiency. Discharge temperature decreases while suction temperature increases—opposite to normal behaviour.
    4.1.3?Lubrication Failure
    Carbonized or emulsified refrigerant oil destroys the oil film; metal-to-metal contact leads to seizure. Oil level and colour observed through the sight glass provide early warning.
    4.2?Refrigerant Anomalies
    4.2.1?Leakage
    Micro-cracks in welds, aged gaskets or cracked valve stems (especially of the hot-gas-bypass solenoid) cause gradual loss. When the charge falls below 80 % of design, evaporator superheat rises sharply and suction pressure collapses.
    4.2.2?Ice and Dirt Blockage
    Moisture >50 ppm forms ice crystals at the expansion orifice; particulate debris causes oil slugs. Both manifest as a sudden evaporator-pressure drop and frequent compressor cycling.
    4.2.3?Non-condensables
    Inadequate evacuation leaves residual air, raising condensing pressure and compressor power while lowering cooling rate.
    4.3?Control System Faults
    4.3.1?Sensor Drift
    Ageing temperature or pressure sensors yield erroneous feedback, causing the PID algorithm to issue wrong commands.
    4.3.2?Program Logic Error
    If the hot-gas-bypass valve remains open during the low-temperature dwell, evaporating temperature rises and the set point cannot be maintained.
    5?Diagnostic and Localization Procedure
    5.1?Preliminary Checks
    (1) Power: three-phase unbalance <2 %, no phase loss; (2) Display: log alarm codes and compressor run time; (3) Sight glass: continuous bubbles >5 s·min?1 indicate undercharge.
    5.2?Combined Pressure–Temperature Test
    Digital manifold gauges measure high- and low-side pressures. With ambient dry-bulb temperature, calculate subcooling (normal 3–5 K) and superheat (normal 6–8 K). Subcooling <2 K plus superheat >15 K indicates refrigerant shortage or expansion-valve misadjustment.
    5.3?Infrared Thermography
    Scan compressor shell, condenser outlet and evaporator inlet; abnormal temperature gradients reveal potential leaks or blockages.
    5.4?Vacuum–Pressure Leak Test
    After refrigerant recovery, pressurize with nitrogen to 1.8 MPa; pressure drop <0.03 MPa in 24 h is acceptable. If exceeded, locate leaks with an electronic halogen detector.
    6?Preventive-Maintenance Strategy
    6.1?Refrigerant Management
    (1) Metered charging: refill to nameplate ±5 g using an electronic scale in closed-loop control;
    (2) Moisture control: replace drier filters every 1000 h; target moisture <20 ppm. 6.2?Compressor Maintenance (1) Every 2000 h measure winding insulation with a 500 V megger (target >100 MΩ);
    (2) Every 4000 h analyse oil; replace if acid number >0.05 mgKOH·g?1;
    (3) Every 8000 h renew synthetic oil of identical grade as per OEM specification.
    6.3?Valves and Piping Maintenance
    (1) Replace the entire valve body when the solenoid stem shows cracks—welding repair is prohibited;
    (2) Perform annual penetrant testing (PT) on stainless-steel brazed joints; repair cracks and re-solution-treat.
    6.4?Control-Program Optimization
    Implement “pressure–temperature dual-variable redundancy” in the PLC: if both temperature and pressure sensors indicate anomalies for >30 s, the system shuts down and outputs a fault code, avoiding false trips from single-sensor drift.
    Cooling loss in thermal shock test chambers is usually the result of coupled compressor degradation, refrigerant-cycle anomalies and control-system faults. Using the reverse Carnot cycle as a theoretical framework, a three-dimensional fault tree (electrical–mechanical–refrigerant) reduces fault-location time to within 30 minutes. Standardized leak detection, metered charging, preventive replacement of critical parts and logic upgrades can raise the system MTBF from 4000 h to over 7000 h, providing sustained technical assurance for environmental reliability testing.

    News Recommendation
    An aging test chamber does not refer to a single device but encompasses various testing methods, including xenon lamp aging tests, UV aging tests, high-temperature aging tests, air-exchange aging tests, and salt spray corrosion aging tests.
    Cold and hot shock test chambers utilize high-temperature and low-temperature zones during testing.
    The temperature test chamber is a widely used testing equipment in industrial enterprises. If your company has newly purchased a temperature test chamber, you must understand the precautions during its operation to avoid deviations in test results or equipment damage caused by improper usage.
    A high-low temperature shock test chamber is designed to evaluate the endurance of products under extremely high and extremely low temperature conditions.
    Frost formation in a thermal shock test chamber is a sublimation phenomenon where moisture inside the chamber condenses under low-temperature conditions. But why does this happen? Is it simply because the chamber temperature is too low?
    Product Recommendation
    Telegram WhatsApp Facebook VK LinkedIn
    亚洲精品人成无码中文毛片| 亚洲av无码国产精品夜色午夜 | 欧美日韩亚洲中文字幕二区| 日韩精品无码一本二本三本| 最近2019中文字幕免费大全5| 少妇人妻无码专区视频| 久久精品?ⅴ无码中文字幕| 免费无码又爽又黄又刺激网站 | 人妻少妇乱子伦无码视频专区| 久久精品一区二区三区中文字幕 | 狠狠精品干练久久久无码中文字幕| 日日摸夜夜添无码AVA片| 亚洲va中文字幕无码久久不卡| 50岁人妻丰满熟妇αv无码区| 中文午夜乱理片无码| 中文自拍日本综合| 久久中文精品无码中文字幕| 免费人妻无码不卡中文字幕系| 西西4444www大胆无码| WWW插插插无码视频网站| 国产精品无码无片在线观看| 无码永久免费AV网站| 亚洲第一极品精品无码久久| 免费无码又爽又刺激网站 | 亚洲日韩中文字幕日韩在线| 中文字幕亚洲综合小综合在线| 国产精品无码久久综合| 国产成人无码综合亚洲日韩| 色窝窝无码一区二区三区色欲| 亚洲av无码专区在线播放| 成人无码WWW免费视频| 亚洲日韩精品一区二区三区无码| 久久无码国产专区精品| 无码八A片人妻少妇久久| 人妻丰满熟妇AV无码区HD| 国精品无码一区二区三区在线蜜臀 | 中文字幕在线播放| 在线亚洲欧美中文精品| 成人无码a级毛片免费| 亚洲va无码专区国产乱码| 蜜桃臀无码内射一区二区三区|